Drift Eliminators, made out of rigid PVC, are designed to remove entrained particles from air steam efficiently, with minimum pressure drop, thereby reducing the fan power requirement when the air passes through the Drift Eliminator. Water droplets are separated from the air drift at the three direction change points on the drift eliminator.
For Cross flow tower applications, the almost vertical waFor Cross flow tower applications, the almost vertical wor Cross flow tower applications, the almost vertical water conduits provided by the SRS 100 drift eliminator remove the water droplets out of the drift eliminator area and return them back into the tower and does not allow any re-entry.
The special locking pin arrangement for SRS-100 facilitates quick and simple assembly at site.
Characteristics | SRS-100 |
---|---|
Suggested Cooling Tower Application | Cross flow |
Type Of Structure | P |
Maximum Face Velocity (m/sec) | 4.0 |
Module Length | 600 - 3000 mm |
Module Width | 1200 mm or as required |
Module Depth | 100 mm |
Distance Between Profiles | 35 |
Directional changes for air flow | 3 |
Maximum Continuous Temperature (°C) | 60 |